The T-5800 Pneumatic Receiver Controller is designed to work with remote temperature, humidity or pressure transmitters that are connected to the control inputs (CV). Zape driver ...
The T-5800 Pneumatic Receiver Controller is designed to work with remote temperature, humidity or pressure transmitters that are connected to the control inputs (CV). The controller provides precise control of pneumatic devices. The T-5800 is able to provide limited supply air to low-capacity remote controls, reducing the number of interconnections between air lines between instruments in only one line. The "CV" input accepts the transmitted output of any pneumatic device with a calibrated output from 3 to 15 psig (21 to 105 kPa).
Product selection table
T-5800 Pneumatic Receiver-Controller
Model | Description |
T-5800-1 | Single Input, Proportional |
T-5800-2 | Single Input, Proportional Plus Integral |
T-5800-3 | Dual Input, Proportional |
T-5800-4 | Dual Input, Proportional Plus Integral |
Technical Specifications
T-5800 Series Pneumatic Receiver-Controller
|
||
Action | T-5800-1, -2, Single Input Models | Direct or Reverse Acting, Field Selectable |
T-5800-3, -4, Dual Input Models | Direct or Reverse Acting with Direct or Reverse Readjustment, Field Selectable |
|
Set Point Adjustment | Factory Set Local at Approximately 9 psig (63 kPa), Field Selectable Local or Remote | |
Gain | T-5800-1, -3 (Proportional-Only Models) |
Adjustable From 0.5: 1 to 15: 1, Factory Set at Approximately 10: 1 |
T-5800-2, -4 (Proportional Plus Integral models) |
Adjustable From 0.5: 1 to 15: 1, Factory Set at Approximately 5: 1 | |
Ratio |
Jumper 1: 1 | Variable From 0.1: 1 to 2.5: 1, Factory Set at Approximately 1: 1 |
Jumper 3: 1 | Variable From 0.1: 1 to 6: 1, Factory Set at Approximately 3: 1 | |
Integral Time (T-5800-2, -4 Only) |
Adjustable From 0.01 to 30 Minutes (Per Repeat), Factory Set at Approximately Three Minutes | |
Supply Pressure | 18 to 22 psig (126 to 154 kPa), Nominal 20 psig (140 kPa) Air Supply Must Be Clean, Dry, and Oil-Free |
|
Air Consumption (Does Not Include Air Consumption for Transmitter restrictions) |
T-5800-1 | 45 scim (12 mL / s) |
T-5800-2 | 60 scim (16 mL / s) | |
T-5800-3 | 60 scim (16 mL / s) | |
T-5800-4 | 75 scim (20 mL / s) | |
Output Capacity
|
1000 sc | |
Materials | Bodysuit | Glass-Reinforced Polypropylene |
Cover | Clear Acrylic Thermoplastic | |
mounting | Surface | |
Air Connections | Two Detachable Connectors with Barbed Fittings for 1/4 in. OD Polytubing |
|
Ambient Operating Limits |
Temperature | 50 to 120 ° F (10 to 49 ° C) |
Humidity | 10 to 90% Rh at Maximum Dew Point or 85 ° F (29 ° C) | |
Ambient Storage Temperature Limits | -20 to 150 ° F (-29 to 66 ° C) |
- available as single or dual input models with proportional or proportional plus integral (PI) control
- adjustments for gain, local set point, ratio, master input balance, and integral time are located on the controller face
- provided with hypodermic needle test points for pressure checks
- designed for surface mounting
- action and readjustment are field selectable
- air lines connect to the unit through two detachable connectors, with barbed fittings for 1/4 in. From politubing
- a clear cover protects the components from dust and dirt, and discourages tampering
- output pressure gauge
- discharge air temperature
- humidity
- water temperatures
- pressure
- static pressure of return fans
- return fan volume control
- chilled water temperature control