Temperature monitors and temperature limiters are tested according to Pressure Equipment Directive 97/23 EC, meet the requirements of DIN EN14597 and can thus be used for heating systems according to...
Temperature monitors and temperature limiters are tested according to Pressure Equipment Directive 97/23 EC, meet the requirements of DIN EN14597 and can thus be used for heating systems according to DIN EN12828, for steam and hot water systems and for district heating systems. The devices with safety function (STW, STB) are self monitoring, i.e. in the event of breakage or leaks in the measuring system the circuit is opened and the system is switched off towards the safe side.
Tabela doboru produktu
Model | STW+TR | STB+TW | STB+TR |
Function | Safety temperature monitor and controller |
Safety temperature limiter and monitor |
Safety temperature limiter and controller |
Satting range | 20 … 150°C | 30 … 110°C | 30 … 110°C |
Satting | STW internal TR external |
STW internal TW internal |
STB internal TR external |
Controls accesible from outside |
Satting wheel for TR | Reclosing button | Reclosing button and satting wheel for TR |
Contact | 2 x changeover | NC (STB) and changeover (TW) |
NC (STB) and changeover (TR) |
Reclosing lockout (internal) |
no | yes | yes |
Max. temperature at sensor |
175°C | 130°C | 130°C |
Imersion depth | 150 mm | 150 mm | 150 mm |
Permitted pressure, brass immersion tube |
25 bar | 25 bar | 25 bar |
Permitted pressure, stainless steel immersion tube |
40 bar T5NST |
40 bar T5NST |
40 bar T5NST |
Sealing pipe thermostat with well. For safety temperature control, and in addition high temperature shut-off functionality.