Type |
adjustable range |
reset |
STW 70130 / STW 70130F |
70 … 130 °C |
auto |
STW 2080 / STW 2080F |
20 … 80 °C |
auto |
STB 70130 / STB 70130F |
70 … 130 °C |
manual |
STB 2080 / STB 2080F |
20 … 80 °C |
manual |
Devices of the STW Honeywell / FEMA Series measure temperature. If the sensor temperature exceeds the set value, a snap-action switch opens, interrupting the electrical circuit. As soon the sensor temperature drops by more than 10 K, the snap-action switch again closes automatically. (Also, if the sensor tem-perature drops to below approx. -20 °C, the snap-action switch opens, but closes again automatically after the tem-perature rises again.)
Devices of the STB Honeywell / FEMA Series likewise measure temperature. If the sensor temperature exceeds the set value, a snap-action switch opens, interrupting the electrical circuit, and remains open until reset manually. (Also, if the sensor temperature drops to below approx. -20 °C, the snap-action switch opens, but closes again automatically after the temperature rises again.) To manually reset the device, the sensor temperature must drop by more than approx. 10 K.
Max. switching capacity
230 Vac, 16 A (2.5 A)
Min. switching capacity
24 Vac/dc, 100 mA
Humidity
0...95% rh, non-condensing
Storage / operating temperature
-30 ... +50 C
Overload temperature
10 K above max. adjustable
temperature
Length of capillary
2 m
Min. bend radius of capillary
5 mm
Pipe diameter
15…100 mm
Mounting position
NL 0 / 90 as per DIN 16257