Product comparison
Type | Setting range | Switching differential (mean values) |
Max. permissible pressure |
Materials in contact with medium |
Switching differential not adjustable | ||||
Ex-DCM4016 | 1…16 mbar | 2 mbar | 1 bar | Perbunan +1.4301 |
Ex-DCM4025 | 4…25 mbar | 2 mbar | 1 bar |
Type | Setting range | Switching differential (mean values) |
Max. permissible pressure |
Ex-DNM10 | 1…10 bar | 0.3 bar | 25 bar |
Ex-DNM63 | 16…63 bar | 1.0 bar | 130 bar |
Pressure switches Ex-DCM and Ex-DNM HONEYWELL / FEMA can be installed directly on the pressure line (pressure gauge connection) or on a flat surface with two 4mm Ø screws.
The maximum medium temperature at the pressure sensor must not exceed the permitted ambient temperature at the switching device. Higher medium temperatures are possible provided the above limit values for the switching device are ensured by suitable measures (e.g. siphon).
Parameter
Value
Kind of pressure
overpressure, relative
Pressure connection
internal thread G¼, external thread G½
Electrical connection
terminal connection M16x1,5
Protection class
IP65
Housing material
rugged housing of seawater resistant aluminium die casting GD Al Si 12.
Media temp.
-15 ... 60°C
Media temp. limit
Higher temperatures are possible, provided that the limit is safeguarded by suitable measures (e.g. water tube trap, see Accessories for Pressure Switches / Transmitters)
Ambient temperature
-15 ... 60°C
Ambient temp. limit
at temperatures below 0°C, ensure that no water condensation can arise in the sensor and in the switching device
Switch function/capacity
SPDT Microswitch; capacity 2 A inductive, 3 A resistiv
Certificates
• SIL2 according IEC 61508-2
• IBExU12ATEX1040 according to ATEX 94/9/EC
• IECEx IBE 14.0077
• IBExU12ATEX1040 according to ATEX 94/9/EC
• IECEx IBE 14.0077