Astra Automatyka > Produkty > Sensors and transducers > Pressure > Differential pressure switch for liquid and gas Ex-DDCM HONEYWELL
Differential pressure switch for liquid and gas Ex-DDCM HONEYWELL

FEMA / Honeywell differential pressure monitors Ex-DDCM are suitable for monitoring and controlling differential pressures, flow monitoring and automatic control of filter systems. A double chamber sy...

FEMA / Honeywell differential pressure monitors Ex-DDCM are suitable for monitoring and controlling differential pressures, flow monitoring and automatic control of filter systems. A double chamber system with stainless steel bellows of Perbunan diaphragm detects the difference between the two applied pressures.


Product comparison
Type Setting range Switching
differential
Max. permissible
pressure
Ex-DDCM014 -0.4 … 0.4 bar 0.15 mbar 15 bar
Ex-DDCM1 0.2 …0.6 bar 0.13 mbar 15 bar
Ex-DDCM16 3 … 16 bar 0.6 mbar 25 bar
Ex-DDCM1602 20 … 160 mbar 20 mbar 3 bar
Ex-DDCM252 4 … 25 mbar 2 mbar 0.5 bar
Ex-DDCM4 1 … 4 bar 0.2 mbar 25 bar
Ex-DDCM6 0.5 … 6 bar 0.2 mbar 15 bar
Ex-DDCM6002 100 … 600 mbar 35 mbar 3 bar
Ex-DDCM662 10 … 60 mbar 15 mbar 1.5 bar
Differential pressure switch for liquid and gas Ex-DDCM HONEYWELL

The desired switching pressure is continuously adjustable within the ranges menti-oned in the product summary. All differential pressure monitors can also be used in the vacuum range. The switching differential is not adjustable.

Parameter Value
Kind of pressure differential pressure, relative
Pressure connection internal thread G¼
Electrical connection terminal connection M16x1,5
Protection class IP65
Housing material rugged housing of seawater resistant aluminium die casting GD Al Si 12
Media temp. -15 ... 60°C
Media temp. limit higher temperatures are possible, provided that the limit is safeguarded by suitable measures (e.g. water tube trap, see Accessories for Pressure Switches / Transmitters)
Ambient temperature -15 ... 60°C
Ambient temp. limit at temperatures below 0°C , ensure that no water condensation can arise in the sensor and in the switching device
Switch function/capacity SPDT Microswitch; capacity 2 A inductive, 3 A resistive
Certificates • SIL2 according IEC 61508-2
• IBExU12ATEX1040 according to ATEX 94/9/EC
• IECEx IBE 14.0077