The Honeywell V5012C controller is used in systems with variable flow, e.g. 2-pipe heating systems or systems with exchangers. The regulator's task is to maintain a constant ...
The Honeywell V5012C controller is used in systems with variable flow, e.g. 2-pipe heating systems or systems with exchangers. The regulator's task is to maintain a constant set differential pressure difference, regardless of changing hydraulic resistance in the system.
Product selection table
Model | Differential pressure- setting range kPa |
Temperature of the medium |
V5012C0103 | 10 ... 30 | -20… 130 ° C |
V5012C0306 | 30 ... 60 | -20… 130 ° C |
Accessories
Model | Description |
VA2502A001 | spring to lower the differential pressure setting by 5 kPa, for a dia. 6 x 1 mm |
VA2502A002 | spring to lower the differential pressure setting by 5 kPa, for a dia. 4 x 1 mm |
VA2503A001 | external connection for mounting between Kombi-dP controller and impulse tube, only for V5012C0103 |
VA2504A001 | angle adapter |
- Can be replaced without interrupting the operation of the installation
- Two possible setting ranges: 10 ... 30 kPa (with the use of a spring 5 ... 25 kPa) or 30 ... 60 kPa
- Durable housing made of stainless steel
- It can be combined with Kombi-3-plus BLUE DN10… DN40 and Komb i-2-plus DN15… DN40
The Kombi-DP diaphragm can be mounted on the valve at any time, even while the system is operating. It is not necessary to drain the system to install the Kombi-DP membrane.
V5012C0396: 0,3 ... 0,6 bar;
V5012C0306: 0,3 bar;